MRC-2013-Catalog - page 212

212
ELECTRONICS
E
DW-6093, 3 phase power analyzer, 3 phase/4 wire, 3 phase/3 wire,
RS232/USB 1 phase/2 wire, 1 phase/3 wire, SD card data recorder
Analysis for 3 phase multi-power system, 1P/2W, 1P/3W, 3P/3W, 3P/4W.
Voltage & Current are the True RMS value.
True Power (KW, MW, GW) measurement.
Apparent Power ( KVA, MVA, GVA) measurement.
Reactive Power ( KVAR, MVAR, GVAR) measurement.
Watt-Hour ( WH, SH, QH, PFH ).
Power Factor (PF), Phase Angle(
Φ
).
Voltage measurement range: 10 to 600 ACV.
Current probe input signal volage (ACV): 200mV/300mV/500mV/1 V/2 V/3 V.
Current probe input current range (ACA): 20A/200A/2000A(1200A)/30A/300A/3000A.
Meter can cooperate the universal current probe.
Programmable CT ratio (1 to 600) and PT ratio (1 to 1000).
ACV input impedance is 10 Mega ohms.
Safety Standard: IEC 1010, CAT III 600V.
Built-in clock & Calendar, real time data record with SD memory card,
sampling time set from 2 to 7200 seconds. Just slot in the SD card into
the computer, it can down load the all the measured value with the
time information (year/month/data/hour/minute/second) to the Excel
directly, then user can make the further data analysis by themselves.
Complete set with 4 PCs Test Leads, 4 PCs Alligator clips, 3 PCs Clamp
Probe, AC to DC 9V adapter, 2 G SD memory card and Carrying bag.
Computer data output, can cooperate with USB Cable/USB-01
RS232 cable/UPCB-02 and Data Acquisition software, SW-U811-WIN.
3 Phase Power Analyzer
DW-6093
Model
DW-6093
Circuit
Custom one-chip of microprocessor LSI circuit.
Display
LCD size : 81.4 X 61 mm (3.2 X 2.4 inch) * Dot Matrix LCD (320 X 240 pixels) with back light.
Measurement
* ACV * ACA * AC WATT (True Power) AC WATT(Apparent Power) AC
WATT(Reactive Power) * Power factor * Phase angle * Frequency
Wire connections
1P/2W, 1P/3W, 3P/3W, 3P/4W.
Voltage ranges
10 ACV to 600 ACV, auto range.
Current probe
input signal & range
* Current probe input signal voltage (ACV): 200mV/300mV/500mV/1V/2V/3V.
* Current probe input current range (ACA): 20 A/200A/2000A (1200A)/30A/300A/3000A
* Meter can cooperate the universal current probe.
Safety standard
IEC1010 CAT III 600 V.
ACV input impedance
10 Mega ohms.
Range select
ACV: Auto range; ACA: Manual range
Clamp frequency response
40 Hz to 1 KHz.
Spec. tested frequency
45 to 65 Hz.
Over load protection
ACV: 720 ACV rms; ACA: 1300 ACA with clamp probe * For the Clamp ,CP-1201
Over Indicator
* LCD display show “OL“.
* The data save into the SD card will show ”9999“ or “999“ (overleap the decimal point).
Under Indicator
* LCD display show “UR“.
* The data save into the SD card will show ”9999“ or “999“ (overleap the decimal point).
Data Hold / Data Record
Freeze the display reading. / SD Card Record.
Sampling Time
Approx. 1 second.
Power ON/OFF
Manual OFF by push button.
Real time datalogger
* Real time datalogger, saved the data into SD memory card & down load the all the measured
value with the time information (year/month/data/hour/minute/second) down load to the Excel
* Integration time for datalogger: 2 seconds to 7200 seconds, the during of setting step are 2 sec.
Data Output USB/RS232
* Computer interface
RS 232/USB PC computer interface. * Connect the optional RS232 cable UPCB-02 will get the
RS232 plug * Connect the optional USB cable USB-01 will get the USB plug.
Operating Temperature
0 to 50°C (32 to 122°F).
Operating Humidity
Less than 80% R.H.
Power Supply
* DC 1.5V, AA (UM-3) BatteryX8 PCs (Alkaline or heavy-duty battery) * AC to DC 9V power adapter
Power Consumption
* Meter: 300 DCmA. * Clamp: 34 DCmA.
Clamp max. conductor Size
50 mm (2.0 inch) Dia. * For the Clamp ,CP-1201
Weight
* Meter: 948g (includes batteries) * Clamp (included cable): 467g
Dimension
Meter: 225 X 125 X 64 mm (8.86 X 4.92 X 2.52 inch)
Clamp : 210 X 64 X 33mm ( 8.3 X 2.5 X 1.3 inch )
Clamp Jaw : 86 mm (3.4 inch)- outside
Accessories Included
* Instruction manual: 1PC * Test Leads (TL88-4AT): 1 Set (4 PCs)
* Alligator clips (TL88-4AC): 1 Set (4 PCs) * Clamp Probe (CP-1201): 3 PCs
* AC to DC 9V adapter: 1 PC * SD card (2G): 1 PC * Carrying bag: 1 PC
Optional Accessories
* 2000 Amp current probe, CP-2000 * 200 Amp current probe, CP-200
* Flexible 3000 Amp current probe, CP-3000 * USB Cable , USB-01
* RS232 cable, UPCB-02 * Data Acquisition software, SW-U811
1...,202,203,204,205,206,207,208,209,210,211 213,214,215,216,217,218,219,220,221,222,...738